Home    Instrumentation    Temperature Measurement    TM101 iTHERM ModuLine
TM10101

TM101 iTHERM ModuLine

RTD or thermocouple temperature probe for direct installation without thermowell in various industrial applications

Field of application

Basic thermometers offer reliable temperature measurement performance with basic sensor technology, a standard extension neck and a fixed, non-replaceable insert for use in non-hazardous areas. The devices are available with optional Bluetooth®-enabled head transmitters with 4 to 20 mA output or HART® communication, providing enhanced measurement accuracy and reliability compared to directly wired sensors.

  • Wide range of applications

  • Measuring range: -50 to +650 °C (-58 to +1202 °F)

  • Pressure range: up to 50 bar (725 psi)

  • Protection class: up to IP68

  • For use in non-hazardous areas

Benefits

  • Excellent value for money and fast global delivery

  • User-friendly product selection, smart design for easy maintenance

  • Wide range of process connections

  • Bluetooth® connectivity (optional)

  • Measuring principle

    Resistance Temperature Detector

  • Characteristic / Application

    Basic technologie
    metric style
    universal range of application
    direct process contact

  • Thermowell / protection tube

    without, direct process contact

  • Insert / probe

    Basis Sensortechnologie

  • Outer diameter protection tube / Insert

    Insert:
    6,0 mm

  • Max. immersion length on request

    up to 1.000,0 mm (39'')

  • Material protection tube/ thermowell

    Insert Material:
    316L (1.4404)
    Alloy 600 (2.4816)

  • Process connection

    Thread:
    G1/2", G1/4"
    NPT1/2"
    M18x1.5, M20x1.5
    Cap-nut:
    G1/2", G3/4"
    Compression fitting, also spring load:
    NPT1/2", G1/2"

  • Tip shape

    straight

  • Operating temperature range

    Basic PT100 TF:
    -50 °C …200 °C
    (-58 °F …392 °F)
    Typ K:
    max. 1.100 °C
    (max. 2.012 °F)

  • Max. process pressure (static)

    depending on the configuration

  • Accuracy

    Class A acc. to IEC 60751
    Class B acc. to IEC 60751
    Class standard acc. to ASTM E230
    Class 2 acc. to IEC 60584-2

  • Response time

    t90 around 17 s
    depending on configuration

  • Integration head transmitter

    yes (4 … 20 mA; HART)